| Motor Connecting Cables | |||
| 2YSLCY-JB/2YSLCYK-JB | 9YSLCY-JB | PENDANT CABLE |
Mineral insulated cables
Constant Wattage Heating Cable up to 260 °C
Application
Vessels, piping, valves
Food processing industry
Frost protection and temperature maintenance on pumps
Standard
DIN VDE 0721-52
EN 62395-1; 2007-05
Voltage Rating
230V
CABLE CONSTRUCTION

Bus wire.
Insulation: Fluoropolymer.
Heating conductor.
Protective: Nickel-plated copper braid.
Outer sheath: Fluoropolymer.
Mechanical and Thermal Properties
Nominal temperature: 260℃
Minimum installation temperature: -45℃
Minimum start-up temperature: -45℃
Bus wire cross section: 2x1.5 mm²
Minimum bending radius: 25mm
Cable Parameter
APPROX. |
Contact spacing m |
Nominal output W/m |
Maximum working temperature |
Maximum heating circuit length m |
|
|---|---|---|---|---|---|
at 50 °C |
at 150 °C |
||||
8.0x5.5 |
1.0 |
15 |
205 |
161 |
119 |
8.0x5.5 |
1.0 |
30 |
190 |
98 |
82.5 |
8.0x5.5 |
1.0 |
45 |
175 |
65.5 |
65.5 |
8.0x5.5 |
1.0 |
60 |
160 |
50 |
50 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information